DSpace logo

Please use this identifier to cite or link to this item: http://142.54.178.187:9060/xmlui/handle/123456789/1084
Title: Non-destructive depth detection approach for substation grounding grids based on magnetostatics
Authors: Qamar, A.
Khan, W.
Naqvi, S.R.
Orakzai, F.Alam
Keywords: COMSATS
substation protection
substation protection
earthing
conductors (electric)
power grids
magnetic flux
Issue Date: 14-Oct-2019
Publisher: IET
Abstract: Grounding grid depth is one of the important factors to diagnose the grounding grid faults. However, due to the drawing loss and back fill during the reconstruction, the real buried depth of the grounding grid is changed and unknown. A magnetostatic method to calculate grounding grid depth is proposed in this Letter. Initially, the proposed method is applied on a single buried conductor where the depth is calculated from the extremum points in the surface magnetic flux density function. Furthermore, the branch current is calculated from the main peak value in the derivative of magnetic flux density function. Finally, a comparative analysis is performed regarding grounding grid depth and branch current. It is shown that the horizontal component of surface magnetic flux density yields results with low error as compared to the vertical component.
URI: http://142.54.178.187:9060/xmlui/handle/123456789/1084
ISSN: 0013-5194
Appears in Collections:Journals

Files in This Item:
File Description SizeFormat 
8866804.htm115 BHTMLView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.